GR33U2
Power Line Monitoring
Recorder &
Data Logger
|
| 6877-1 Goreway Drive, Mississauga, Ontario, Canada
L4V 1L9
Tel: (905) 677-5533, Fax: (905) 677-5030, e-mail: rms@rmsinst.com |
Features
|
|
GR33U2 Power Line Monitoring Recorder
The GR33U2 Power Line Monitoring Recorder with its selection of signal conditioning inputs (Voltage, Frequency), offers reliable, low-maintenance, thermal array recording technology. The high resolution thermal head has a printing width of 296 mm (11.65 inches) with 8 printing elements or dots per mm (203 per inch). The grid is printed simultaneously with the signal waveforms, eliminating any drift between waveforms and grid.
The analog section has a 16 bit A/D converter per channel which is self calibrating, ensuring high accuracy and long term stability.
Alphanumeric labeling of the traces and chart can be readily entered from the keyboard, terminal or computer.
The operation of the recorder is controlled by a unique and compact control panel. A single rotary control scrolls through the recorder menus, allowing the user to quickly alter items such as chart speed and grids. This technique eliminates the numerous front panel controls usually found on this type of recorder
Alternatively, the recorder can be controlled externally by a host computer or by a PC using the optional PC33 Control and Interface Software.
Also available is the DISP33 Virtual Chart Recorder Display program that graphically displays data from the recorder in real-time. The program uses an PC to create a display that resembles the output of the chart recorder - vertical traces on the chart.
This results in a versatile, accurate, reliable and low maintenance recorder with a wide chart presentation, with high resolution and easy viewing.

Data Logging
In addition to producing hard copy, the recorder may also be operated in a logging mode where data for up to 320 days is kept in battery-backed memory. The log data is tagged with time, date and "Station I.D.". The data may be periodically retrieved on a daily, weekly etc. basis by an external computer with a standard RS232 port or via a modem.
Remote Real-Time Monitoring
The trace data can be transmitted by the serial port or a modem to a remote host computer for monitoring or recording. The transmission interval is user selectable.
Both the data logging and real-time outputs will operate with or without
paper recording. In addition, these two features have a simplified
command set and status alarms provided for the host computer.
Recorder Specifications
GR33U2 Power Line Monitoring
Recorder & Data Logger
| RECORD: | |
|
Recording Method:
|
Thermal array technology consisting of 2368 printing elements on 0.125 mm centres with 203 dots per in. (8 dots per mm). |
|
Size:
|
11.65 in. (296 mm) record on 12.625 in. (321 mm) paper. |
|
Resolution:
|
200 x 200 dots per in. in both axis at all speeds (approximate). |
|
Number of Channels: *
|
2 traces with alphanumeric capability. |
|
Grid Description and
Printing: * |
4 pre-defined grids selectable from front panel printed simultaneously
with waveform. Each channel has 140 mm wide grid, with 4 major divisions,
and 20 minor divisions to each major division. The four styles of
annotation for grid scaling are;
a) 100,110,120,130,140 VAC; 100,110,120,130,140 VAC b) 11.50,12.65,13.80,14.95,16.10 KV; 55.00,57.50,60.00,62.50,65.00 HZ. c) 12.0,13.2,14.4,15.6,16.8 KV; 55.0,57.5,60.00,62.5,65.0 HZ. d) 200, 210, 220, 230, 240 VAC; 200, 210, 220, 230, 240 VAC. |
|
Paper:
|
Plain thermal sensitive roll paper 12.625 in. (321 mm) wide by 200 ft. (60 m) long, Part No: RMS2030-4 |
|
Chart Annotation: *
|
a) Trace identification by a four character label printed vertically
next to each channel. This is alterable via the front panel, a host computer
or by a PC using the optional PC33 Interface and Control Software.
printed approx. every 60 mm.
b) Selectable Time, Time and Date or Date, printed vertically on right hand side. Printing interval is programmable. c) 8 character programmable "Station I.D.", printed with time. |
| PAPER TRANSPORT: | |
|
Paper Viewing Area:
|
3.3 in. (84 mm) using take-up spool. |
|
Drive Mechanism:
|
Roller type, driven by microprocessor controlled stepper motor with an internal take-up spool. |
|
Chart Speeds:
|
a) Fixed - 1, 5 mm/min & 25 mm/sec.
b) Variable - 0.01 mm/sec - 25.0 mm/sec in 0.01 increments. c) Paper advance at 25 mm/sec activated by push button with or without simultaneous printing. d) Chart On/Off - local or remote. e) millimeters or inches - user selectable. |
|
Paper Level:
|
4 segment LED bargraph paper level indicator using solid state level sensor. Alarm indicating out of paper. |
| INSTALLATION: | |
|
Size:
|
19 in. (482.6 mm) rack mountable x 5.25 in. (133.4 mm) high. Overall depth 19.3 in. (490 mm), extending 17.5 in. (445 mm) behind mounting surface. |
|
Weight:
|
approximately 24.5 lbs (11.2 kg.). |
|
Finish:
|
Black anodized. |
| POWER REQUIREMENTS: | 85-250 VAC, 47-440 Hz and 110-330 VDC; typically 100 watts. |
| ENVIRONMENT: | |
|
Operating Temperature:
|
0°C to +50°C, thermostatically controlled cooling fan |
|
Storage Temperature:
|
-40°C to +60°C Humidity: 5% to 95% non-condensing. |
|
Vibration:
|
10 cycles of 6 hour cycles, each cycle consists of 4 hours at +40°C with 10 minutes of vibration at 1g, 60 Hz every hour, and one hour cold cycle to 0°C. |
| DIGITAL INPUT: | 1) Parallel port to be used with a host computer or a PC using the
optional PC33 Interface and Control Program Software.
2) Serial port to be used with host computer as control port. Transfer Rate: 300 to 19.2 kbps |
| DIGITAL OUTPUT: | Serial port for data logger memory and real time data transmission.
ASCII or binary format Transfer Rate: 300 to 19.2 kbps |
| DATA LOGGING CAPACITY: | 120 Kbytes
Recording time dependent on chart speed and user selectable K factor - e.g. 30 Hrs (1mm/min, K=1) 320 days (1 mm/min, K=256) |
| ANALOG INPUT: | |
|
Number:
|
two analog signals via rear panel (one A/D converter per channel). |
|
Input Voltage Range: *
|
nominally 110 VAC - measuring over the range of 100 to 140 VAC, or
nominally 220 VAC - measuring over the range of 200 - 240 VAC. |
|
Real-time Bandwidth:
|
DC - 500Hz per channel (-3dB). |
|
A/D Resolution:
|
16 bits, self calibrating |
| FREQUENCY INPUT: (optional) | |
|
Sensitivity:
|
nominally 60 Hz - measuring over the range of 55 to 65 Hz, or 50 Hz - measuring over the range of 45 to 55 Hz. |
| FRONT PANEL CONTROLS
& INDICATORS: |
- paper advance push button (25mm/sec).
- illuminated power On/Off switch. - LED 4 segment paper level gauge - Chart On/Off. - operator control panel consisting of a 12 digit alphanumeric display and a rotary control to scroll system items, for example, real-time clock, grids, chart speed etc. |
| REAR PANEL: | |
|
Exposed:
|
- 12 point screw-type terminal block for the two signal inputs,
power, misc. control signals.
- 25 pin `D' type connector; parallel control port. - 9 pin `D' type connector; serial output port. - 9 pin `D' type connector; serial control port. |
Optional Accessories
Specifications subject to change without notice.
|
|
|
|
|
|
|
|